Skip to content

IPEM Serial Monitor Example

Dave Williams | DitroniX | G8PUO edited this page May 23, 2023 · 1 revision

DitroniX IPEM-1 ATM90E32 ATM90E36 IoT Power Energy Monitor Board - Development Code

Attempting to connect to TestAP ... Connected to TestAP

Connection Details:

  • WiFi SSID TestAP (Wifi Station Mode)
  • WiFi IP 192.168.1.61 (Static)
  • WiFi MASK 255.255.255.0
  • WiFi GW 192.168.1.1
  • WiFi DNS 1 192.168.1.1
  • WiFi DNS 2 8.8.4.4
  • WiFi MAC 16:3A:8D:16:9A:08
  • WiFi Hostname IPEM-9A08
  • WiFi RSSI -78 dBm (Signal Good)

Initialise WebServer

Register Status and Startup Report

  • IPEM-1 ATM90E32 ATM90E36 IoT Power Energy Monitor
  • ESP32 Serial ID: 089A858D3A08 Firmware Version: 230522
  • Board Location: House

Wi-Fi is Enabled

Domoticz Publishing is Disabled

EEPROM Check: 20 (Validation OK)

Peripherals Test

  • Testing RGB LED
  • Scanning I2C Bus for Devices ...
    • I2C device found at address Decimal 60 = Hex 0x3C OLED
    • I2C device found at address Decimal 80 = Hex 0x50 EEPROM
    • I2C Bus Scan Complete

AC/DC Voltage Input Detected

Connecting to the ATM90E32

ATM90E32 Connected - OK

IPEM Hardware Setup and Power-Up Test - Board Initialized

Mains RMS Voltage

  • Voltage 1: 246.15 V (Single Line Voltage Selected)

Mains RMS Current

  • Current CT1: 1.29 A
  • Current CT2: 1.29 A
  • Current CT3: 1.29 A
  • Actual Total Current: 3.87 A (CT1CT2CT3)

Calculated RMS Power

  • Power V1*I1: 317.53 W
  • Power V1*I2: 317.53 W
  • Power V1*I3: 317.53 W
  • Calculated Total Power: 957.19 W (CT1CT2CT3)

Active Power (Absorbed or Used by the Load)

  • Active Power CT1: 315.52 W (Import)
  • Active Power CT2: 318.92 W (Import)
  • Active Power CT3: 320.92 W (Import)
  • Total Active Power: 636.44 W (Import)
  • Calculated Total Active Power: 955.36 W (CT1CT2CT3)

Re-Active Power

  • ReActive Power CT1: 18.95 VAR
  • ReActive Power CT2: 18.35 VAR
  • ReActive Power CT3: 19.07 VAR
  • Total ReActive Power: 38.00 VAR (CT1CT2CT3)
  • Calculated Total Reactive Power: 56.37 W (CT1CT2CT3)

Apparent Power (Total Amount of Power Flowing from Source to Load)

  • Apparent Power CT1: 316.15 VA
  • Apparent Power CT2: 319.50 VA
  • Apparent Power CT3: 321.38 VA
  • Total Apparent Power: 637.60 VA (CT1CT2CT3)
  • Calculated Total Apparent Power: 957.03 W (CT1CT2CT3)

Other Power Information

  • Total Fundamental Power: 635.67 pH(t)
  • Total Harmonic Power: 0.95

Power Factor

  • Power Factor CT1: 1.00 PF
  • Power Factor CT2: 1.00 PF
  • Power Factor CT3: 1.00 PF
  • Total Power Factor: 1.00 PF

Phase Angle

  • Phase Angle CT1: 3.40
  • Phase Angle CT2: 3.20
  • Phase Angle CT3: 3.30

Other Information

  • Chip Temperature: 27.00 °C
  • Mains Frequency: 49.98 Hz
  • PCB Temperature Sensor (NTC_IN VN): 24.60 ºC
  • ADC Raw: 2673 > ADC Adjusted: 2673 > Calculated: 25.46 V