function Tr = Tr_GMTD(q,Ts,Ti,qo,Tso,Tro,Tio,n)
%% Calculates the return temperature from the radiator unit
% emprical equation based on GMTD
% Ref: Phetteplace - Optimal Design of Piping Systems for District Heating
% prepared by Hakan ibrahim Tol, PhD
%% INPUT&OUTPUT
% Input
% q : Heat demand - actual condition [kW]
% Ts : Supply temperature - actual condition [degC]
% Ti : Set degree of indoor temperature - actual [degC]
% qo : Heat demand - design condition [kW]
% Tso : Supply temperature - design condition [degC]
% Tro : Return temperature - design condition [degC]
% Tio : Set degree of indoor temperature - design [degC]
% n : Emprical radiator constant [-]
% Output
% Tr : Radiator return temperature - actual [degC]
%% Calculation for original condition
GMTDo=tGMTD(Tso,Tro,Tio);
%% Calculate Tr
Tr=Ti+((Ts-Ti)^(-1)*GMTDo^2*(q/qo)^(2/n));
if Tr>=Ts
Tr=NaN;
return
end
%% Evaluation of error (AF: Approach Factor)
AF=(Tr-Ti)/(Ts-Ti);
if AF>=0.33
fprintf('User Warning: Approach factor is %f - Error less than 0.05',AF);
else
fprintf('User Warning: Approach factor is %f - Error larger than 0.05',AF);
end
end