Converting openPDC Database
Stephen Jenks edited this page Jan 17, 2017
·
2 revisions
If you have been using the Historian 1.0 included in the openPDC, want to upgrade to Historian 2.0 in the openHistorian, and want to keep access to your old data from the openHistorian, you need to convert the database openPDC is using so that the openHistorian can use it. Here is how you do it:
- Stop the openPDC and openHistorian services.
- Make a copy of the openPDC database.
- Use the openHistorian Configuration Setup Utility to have the openHistorian use the copy of the openPDC database. Uncheck the "Start the openHistorian" and "Start the openHistorianManager" boxes at the last step
- Start the openHistorian Manager.
- Go to
Inputs
->Subscription Based Inputs
->Create Internal Subscription
. - Enter "PDC" for the
Name
andAcronym
, enter "xyz" for theHostname
(This will be changed later), enter "6165" for thePort
, leave theUDP Port
checkbox unchecked and save.
- Select "PPA" as the
Historian
and save.
- Go to
Inputs
->Browse Input Devices
.- For each input device that is not a concentrator, change the
Concentrator
to "PDC" and save.
- Disable all concentrators besides "PDC".
- For each input device that is not a concentrator, change the
- Go to
System
->Manage Nodes
. - Change the port numbers to 8510, 6175, and 5019 and save.
- Go to
Outputs
->Historian Instances
. - Select "PPA", change the
Type Name
to "openHistorian.Adapters.LocalOutputAdapter" and theAssembly Name
to "openHistorian.Adapters.dll" and save.
- Go to
Inputs
->Browse Input Devices
. - Select "PDC"
- In the connection string, change the
server
from "xyz" to the machine that the openPDC service is running on, in my case, localhost.
- Restart the openPDC and openHistorian services.