Expand Up @@ -547,7 +547,7 @@ Algorithm call: {py:class}`CalculationMethod.iec60909 <power_grid_model.enum.Cal

The assumptions used for calculations in power-grid-model are aligned to the ones mentioned in [IEC 60909](https://webstore.iec.ch/publication/24100).

- The state of grid with respect to loads and generations are ignored for the short circuit calculation. (Note: Shunt admittances are included in calculation.)
- The state of the grid with respect to loads and generations are ignored for the short circuit calculation. (Note: Shunt admittances are included in calculation.)
- The pre-fault voltage is considered in the calculation and is calculated based on the grid parameters and topology. (Excl. loads and generation)
- The calculations are assumed to be time-independent. (Voltages are sine throughout with the fault occurring at a zero crossing of the voltage, the complexity of rotating machines and harmonics are neglected, etc.)
- To account for the different operational conditions, a voltage scaling factor of `c` is applied to the voltage source while running short circuit calculation function.
Expand All @@ -563,12 +563,12 @@ The assumptions used for calculations in power-grid-model are aligned to the one
In the IEC 609090 standard, there is a difference in `c` (for `U_nom` <= 1kV) for systems with a voltage tolerance of 6% and 10%. In power-grid-model we only use the value for a 10% voltage tolerance.
```

There are 4 types of fault situations that can occur in the grid, along with the following possible combinations of the associated phases:
There are {py:class}`4 types <power_grid_model.enum.FaultType>` of fault situations that can occur in the grid, along with the following possible combinations of the {py:class}`associated phases <power_grid_model.enum.FaultType>`:

- Three-phase to ground: abc
- Single phase to ground: a, b, c
- Two phase: ab, bc, ac
- Two phase to ground: ab, bc, ac
- Three-phase to ground: `abc`
- Single phase to ground: `a`, `b`, `c`
- Two phase: `ab`, `bc`, `ac`
- Two phase to ground: `ab`, `bc`, `ac`

### Regulated power flow calculations

Expand All @@ -591,15 +591,73 @@ Please refer to their respective sections for detailed documentation.
At the time of writing, this feature is still experimental and is not yet publicly available.
```

Some of the most important regulators in the grid affect the tap position of transformers. These {hoverxreftooltip}`user_manual/components:transformer-tap-regulator`s are
Some of the most important regulators in the grid affect the tap position of transformers.
These {hoverxreftooltip}`user_manual/components:Transformer Tap Regulator`s try to regulate a control voltage $U_{\text{control}}$ such that it is within a specified voltage band.
The $U_{\text{control}}$ may be compensated for the voltage drop during transport.
Power flow calculations that take the behavior of these regulators into account may be toggled by providing one of the following strategies to the {py:meth}`tap_changing_strategy <power_grid_model.PowerGridModel.calculate_power_flow>` option.

| Algorithm | Default | Speed | Algorithm call |
| ------------------------------------------------------------ | -------- | -------- | ----------------------------------------------------------------------------------------------------------- |
| No automatic tap changing (regular power flow) | &#10004; | &#10004; | {py:class}`TapChangingStrategy.newton_raphson <power_grid_model.enum.TapChangingStrategy.disabled>` |
| No automatic tap changing (regular power flow) | &#10004; | &#10004; | {py:class}`TapChangingStrategy.disabled <power_grid_model.enum.TapChangingStrategy.disabled>` |
| Optimize tap position for any value in the voltage band | | &#10004; | {py:class}`TapChangingStrategy.any_valid_tap <power_grid_model.enum.TapChangingStrategy.any_valid_tap>` |
| Optimize tap position for lower voltage in the voltage band | | | {py:class}`TapChangingStrategy.min_voltage_tap <power_grid_model.enum.TapChangingStrategy.min_voltage_tap>` |
| Optimize tap position for higher voltage in the voltage band | | | {py:class}`TapChangingStrategy.max_voltage_tap <power_grid_model.enum.TapChangingStrategy.max_voltage_tap>` |

The following control logic is used.

- Regulated transformers are ranked according to the amount of transformers between itself and the nearest source {hoverxreftooltip}`user_manual/components:source`.
- Transformers that are closer to a {hoverxreftooltip}`user_manual/components:source` are regulated first.
- Initialize all transformers to their starting tap position (see {hoverxreftooltip}`user_manual/calculations:Initialization and exploitation of regulated transformers`)
- Find the optimal state using the following procedure
- While not all transformers are regulated, iterate as follows:
- Run a power flow calculation with the current tap positions with the specified [calculation method](#power-flow-algorithms).
- Start with the lowest rank (with the transformers closest to a {hoverxreftooltip}`user_manual/components:source`, because the source provides a relatively stable voltage level).
- Loop over all ranks:
- Loop over all transformers within this rank; transformers with the same rank are independently regulated:
- If the $U_{\text{control}} < U_{\text{set}} - \frac{U_{\text{band}}}{2}$:
- The ratio between the voltage on the tap side and the voltage on the control side is too high.
- To decrease this ratio, the tap ratio must be decreased.
- Therefore, the tap position of the regulated transformer is decreased if it satisfies the bounds set by `tap_min` and `tap_max`.
- If, however, the $U_{\text{control}} > U_{\text{set}} + \frac{U_{\text{band}}}{2}$:
- The ratio between the voltage on the tap side and the voltage on the control side is too low.
- To increase this ratio, the tap ratio must be increase.
- Therefore, the tap position of the regulated transformer is increased if it satisfies the bounds set by `tap_min` and `tap_max`.
- If the tap position of this transformer did not change, the transformer is considered regulated.
- If not all transformers within this rank are regulated, step out of the loop and go to the next iteration step.
- Exploit the neighbourhood of all transformers (see {hoverxreftooltip}`user_manual/calculations:Initialization and exploitation of regulated transformers`)
- Re-run the iteration in the above if any of the tap positions changed by the exploitation.

The exploitation of the neighbourhood ensures that the actual optimum is not accidentally missed due to feedback mechanisms in the grid.

```note
For iterative [power flow calculation methods](#power-flow-algorithms), the initial state may not converge.
If the iterative process failed to converge, the optimization procedure is executed twice.
First, the {py:class}`linear <power_grid_model.enum.CalculationMethod.linear>` calculation method is used to find an approximate solution.
The optimization procedure is then run a second time to find the actual optimum with the user-specified calculation method.
```

```note
The control logic assumes that the change in voltage level caused by changing a transformer is larger than the change caused by adjacent transformers.
This is assumption is reflected in the requirements mentioned in {hoverxreftooltip}`user_manual/components:Transformer Tap Regulator`.
```

```note
The control logic assumes that the (compensated) control voltage decreases when the tap position increases.
If the line drop compensation impedance is high, and the control side has generator-like behavior, then this assumption does not hold, and the calculation may diverge.
Hence, this is assumption is reflected in the requirements mentioned in {hoverxreftooltip}`user_manual/components:Line drop compensation`.
```

##### Initialization and exploitation of regulated transformers

Regulated transformers are initialized and exploited depending on the optimization strategy.

| strategy | initial tap position | exploitation direction | description |
| ----------------------------------------------------------------------------------------------------------- | -------------------- | ---------------------- |
| {py:class}`TapChangingStrategy.any_valid_tap <power_grid_model.enum.TapChangingStrategy.any_valid_tap>` | current tap position | no exploitation | |
| {py:class}`TapChangingStrategy.min_voltage_tap <power_grid_model.enum.TapChangingStrategy.min_voltage_tap>` | `tap_max` | step up | Highest tap side voltage means lowest control voltage (closest to lower voltage band) |
| {py:class}`TapChangingStrategy.max_voltage_tap <power_grid_model.enum.TapChangingStrategy.max_voltage_tap>` | `tap_min` | step down | Lowest tap side voltage means highest control voltage (closest to upper voltage band) |