Triangle MicroWorks SCADA Data Gateway...
High severity
Unreviewed
Published
May 3, 2024
to the GitHub Advisory Database
•
Updated May 3, 2024
Description
Published by the National Vulnerability Database
May 3, 2024
Published to the GitHub Advisory Database
May 3, 2024
Last updated
May 3, 2024
Triangle MicroWorks SCADA Data Gateway GTWWebMonitorService Unquoted Search Path Remote Code Execution Vulnerability. This vulnerability allows remote attackers to execute code on affected installations of Triangle MicroWorks SCADA Data Gateway. Although authentication is required to exploit this vulnerability, the existing authentication mechanism can be bypassed.
The specific flaw exists within the configuration of the GTWWebMonitorService service. The path to the service executable contains spaces not surrounded by quotations. An attacker can leverage this vulnerability to execute arbitrary code in the context of root. Was ZDI-CAN-20538.